Kyoritsu 3007A Insulation/Continuity Tester
Bar graph to display insulation resistance.
Displays the value of external AC voltage along with flashing symbol.
Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
Trac-Lok mode to conserve battery life on insulation and continuity tests.
Live circuit warning beeper.

Kyoritsu 3007A product photo

 

More Info
Kyoritsu 3007A Product Summary
Kyoritsu 3007A Product Literature
Repair and Calibration Service

 

Releasing the test button automatically discharges the charges stored in the circuit under test.
Backlight function to view the test results in dimly lit areas.
200mA continuity measuring current to IEC 61557.
Minimum 1mA current on insulation tests to IEC 61557.

 

Insulation Resistance
Test Voltage 250V/500V/1000V
Measuring Range (Mid-scale Value) 20MΩ/200MΩ/2000MΩ
Output Voltage
on open circuit
Rated test voltage+20%, -0%
Nominal Current 1mA DC min.
Output Short
Circuit Current
1.5 mA DC approx.
Accuracy |±1.5%rdg±5dgt (20MΩ/200MΩ)
|±10%rdg±3dgt (2000MΩ)
Continuity Test
Measuring Ranges
(Mid-scale Value)
20Ω/200Ω/2000Ω
Output Voltage
on open circuit
7~12V DC
Measuring Current 200mA DC min.
Accuracy |±1.5%rdg±5dgt (20Ω)
|±1.5%rdg±3dgt (200Ω/2000Ω)
AC Voltage
AC Voltage 0~600V AC
Accuracy |±5%rdg±3dgt
General
Safety Standard IEC61010-1 CAT.III 300V Pollution Degree 2
IEC61010-2-031
IEC61557-1/2/4
IP Rating IEC60529-IP54
EMC Standard IEC61326-1
Withstand Voltage 3700V AC for 1 minute
Power Source R6P(AA)(1.5V) × 8
Dimensions 185(L) × 167(W) × 89(D)mm
Weight 990g approx
Accessories 7122(Test leads) Pouch for test leads
8923(F500mA/600V fuse) × 2
R6P(AA) × 8
Shoulder Strap
Instruction Manual

 
 
 
Copyright ©2012 Eaton
Industries Pty Ltd.